是否进口:否 | 加工定制:否 | 品牌:sepam |
型号:sepam s40 | 产品名称:sepam | 适用范围:电厂 |
用途:继电保护装置 | 产品认证:ce |
继电保护装置sepam 40系列s40
59680
substation - S40 - Sepam series 40
Characteristics
Main
Relay applicationSubstation
Range of productSepam series 40
Device short nameS40
Control and monitoring typeLogic equation editor 100 operators
Circuit breaker/contactor control ANSI code: 94/69
Annunciation ANSI code: 30
Switching of groups of settings
Logic discrimination ANSI code: 68 ( option )
Latching/acknowledgement ANSI code: 86
Metering typeActive and reactive energy by pulse counting (+/- W.h, +/- VAR.h) ( option )
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Active, reactive, apparent power P,Q,S-peak demand power PM, QM, power factor
Positive sequence voltage Vd/rotation direction-negative sequence voltage Vi
Frequency
Voltage U21, U32, U13, V1, V2, V3, residual voltage V0
Demand current I1, I2, I3, peak demand current IM1, IM2, IM3
Phase current I1, I2, I3 RMS, residual current I0
Network and machine diagnosis typePhase displacement
Tripping context
Disturbance recording
Unbalance ratio/negative sequence current Ii
Switchgear diagnosis typeCT/VT supervision ANSI code: 60FL
Number of operations, operating time charging time ( option )
Trip circuit supervision ( option )
Cumulative breaking current
Complementary
Type of measurementCurrent
Energy
Frequency
Peak demand power
Power (P,Q)
Power factor
Voltage
Protection typeUnderfrequency ANSI code: 81L
Overfrequency ANSI code: 81H
Negative sequence overvoltage ANSI code: 47
Negative sequence/unbalance ANSI code: 46
Earth fault/sensitive earth fault ANSI code: 50G/51G
Earth fault/sensitive earth fault ANSI code: 50N/51N
Phase overcurrent ANSI code: 50/51
Overvoltage protection ANSI code: 59
Undervoltage protection ANSI code: 27/27S
Breaker failure ANSI code: 50BF
Neutral voltage displacement ANSI code: 59N
Recloser (4 cycles) ( option ) ANSI code: 79
Communication port protocolTransfer of disturbance recording data ( option ) : Modbus
Remote protection setting ( option ) : Modbus
Remote control orders ( option ) : Modbus
Remote indication and time tagging of events ( option ) : Modbus
Measurement readout ( option ) : Modbus
Input output max capacity10 inputs + 8 outputs
Communication compatibilityModbus RTU
IEC 60870-5-103
DNP3
IEC 61850
Modbus TCPIP
User machine interface typeAdvanced
Without
Remote
Offer Sustainability
Sustainable offer statusNot Green Premium product