是否进口:否 | 加工定制:否 | 品牌:SND |
型号:PM700MG | 产品名称:功能表 | 适用范围:工业 |
用途: 电力参数测量仪 | 产品认证:ce |
PM700MG
power meter PM750MG - basic readings, THD and min/max
Characteristics
Main
Range of productPowerLogic PM750
Device short namePM750
Product or component typePower meter
Complementary
Power quality analysisTotal harmonic distortion
Type of measurementEnergy
Reactive power (per phase)
Active power (per phase)
Apparent power (per phase)
Reactive power (total)
Active power (total)
Apparent power (total)
Power factor (total)
Frequency
Voltage
Current
Supply voltage115...415 V AC (45...65 Hz)
125...250 V DC
Network frequency45...65 Hz
Power consumption in VA5 VA
Display typeBacklit LCD
Display resolution6 lines
Sampling rate32 samples/cycle
Measurement current5 A
1 A
Input typeCurrent 0.005...6 A (impedance <= 0.1 Ohm)
Measurement voltage10...277 V AC 45...65 Hz phase to neutral
10...480 V AC 45...65 Hz phase to phase
Measurement accuracy± 0.0034 power factor (1A to 6A and from -0.5 to +0.5)
± 0.02 Hz frequency (45...65 Hz)
± 0.5 % voltage (50...227 V)
± 0.5 % current (1...6 A)
± 1 % power
Accuracy classClass 1 (active energy according to IEC 62053-21)
Class 2 (reactive energy according to IEC 62053-23)
Data recordingMin/max of instantaneous values
Environment
Electromagnetic compatibilityLimitation of voltage changes, voltage fluctuations and flicker in low-voltage, conforming to IEC 61000-3-3
Immunity to microbreaks and voltage drops class class III, conforming to IEC 61000-4-11
Immunity to impulse waves class class III, conforming to IEC 61000-4-8
Conducted RF disturbances class class III, conforming to IEC 61000-4-6
1.2/50 ?s shock waves immunity test class class III, conforming to IEC 61000-4-5
Electrical fast transient/burst immunity test class class III, conforming to IEC 61000-4-4
Susceptibility to electromagnetic fields class class III, conforming to IEC 61000-4-3
Electrostatic discharge immunity test class class III, conforming to IEC 61000-4-2
Conducted and radiated emissions, conforming to EN 55011 class B
Limits for harmonic current emissions, conforming to IEC 61000-3-2
Mounting modeFlush-mounted
Mounting supportPanel
Type of installationIndoor installation
Overvoltage categoryIII
IP degree of protectionIP52 (front face) conforming to IEC 60529
IP30 (back) conforming to IEC 60529
Relative humidity95 % 50 °C
Pollution degree2
Ambient air temperature for operation-5...50 °C
Ambient air temperature for storage-40...85 °C
Operating altitude0...3000 m
StandardsIEC 61010-1
UL 508
CSA C22.2 No 14
Product certificationsCE
CULus
Width96 mm
Depth69 mm
Height96 mm
Product weight0.37 kg
Offer Sustainability
Sustainable offer statusGreen Premium product
RoHSCompliant - since 0951 - print Schneider Electric declaration of conformity
REAChReference not containing SVHC above the threshold
Product environmental profileAvailable